MODEL |
AP9940 |
AP9960 |
AP9980 |
AP99120 |
Rated capacity |
40 kVA / 40 kW |
60 kVA / 60 kW |
80 kVA / 80 kW |
120 kVA / 120 kW |
INPUT |
Input wiring |
Three-phase five-wire (3Φ + N + PE) |
Rated voltage |
380 / 400 / 415 Vac |
Voltage range |
305 ~ 485 Vac (no downgrading), 138 ~ 305 Vac (linear downgrading between 40% ~ 100% load) |
Frequency range |
40 ~ 70 Hz |
Power factor |
≥ 0.99 |
THDi |
≤ 3% |
Bypass voltage range |
-60% ~ +20% (settable) |
Battery voltage |
±192 Vdc (±180 ~ ±276 Vdc settable) |
Number of battery |
32 pcs 12 V batteries (30 ~ 46 pcs settable) |
OUTPUT |
Output wiring |
Three-phase five-wire (3Φ + N + PE) |
Rated voltage |
380 / 400 / 415 Vac |
Voltage regulation |
±1% |
Frequency |
Synchronized with utility in mains mode, 50 / 60 Hz ± 0.1% in battery mode |
Power factor |
1.0 |
Total harmonic distortion (THDV) |
≤ 1% (linear load); ≤ 5% (non-linear load) |
Crest factor |
3:1 |
Overload capability |
105% ~ 110% for 60 min, 110% ~ 125% for 10 min, 125% ~ 150% for 1 min, >150% for 0.2 s |
SYSTEM |
Max. efficiency |
96% in online mode, 99% in ECO mode |
Transfer time |
0 ms |
Max. number of parallel connections |
4 |
Protection |
Short-circuit – overload – overtemperature –excessive low battery – overvoltage / undervoltage – fans failure |
Communications |
Standard configuration: RS232, USB, RS485, NET, dry contacts; Optional configuration: SNMP card, Wi-Fi card, GPRS card |
Display |
5 inches colorful LCD touch screen |
OTHERS |
Operating environment |
0 ~ 40℃ |
Storage temperature |
-25℃ ~ 55℃ (without battery) |
Relative humidity |
0% ~ 95% (non-condensing) |
Altitude |
≤ 1000 m; above 1000 m, downgrading 1% for each additional 100 m |
IP rating |
IP 20 |
Noise |
≤ 65 dB (at 1 m) |
Dimensions (W × D × H) (mm) |
360 × 850 × 950 |
360 × 850 × 1200 |
440 × 850 × 1200 |
Packaged dimensions (W × D × H) (mm) |
460 × 950 × 1113 |
460 × 950 × 1363 |
540 × 950 × 1363 |
Net weight (kg) |
93 |
125 |
157 |
192 |
Gross weight (kg) |
106 |
138 |
170 |
207 |