AP9300 10 kVA ~ 30 kVA (3:3)

apollopower.net > APOLLO UPS > Online Transformerless UPS > AP9300 10 kVA ~ 30 kVA (3:3)

AP9300 10 kVA ~ 30 kVA (3:3)

  • DSP digital control technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Cold start
  • Dual input
  • Wide input voltage range (190 V ~ 485 V)
  • Auto sensing frequency
  • 50 / 60 Hz frequency conversion mode
  • Work efficiency up to 98% in ECO mode
  • Auto control fan speed when loads varies
  • Auto power ON/OFF according to the load capacity set by users
  • Flexible battery configuration for using 14/16/18/20 pcs batteries
  • Compact internal layout, miniaturized the complete unit for small footprint
  • LCD+LED display, multi-functional keys operation, friendly human-machine interface
  • Powerful background software for parameters configuration and online updating
  • Doubling the battery charging speed, 90% capacity restored in 4 hours (standard model UPS
  • Linear derating in low voltage input, reducing battery discharging times, extending the service life of battery
  • Advanced battery management (ABM), automatic floating / equalizing charge control, charger dormancy control
  • Configurable switching time from battery mode to mains mode when mains power is restored, reducing the impact on power grid or generator
  • Effective software and hardware protection function, powerful self-diagnostic function, abundant historical records
  • Standard emergency power off (EPO)
  • Standard maintenance bypass
  • Standard RS232/USB communication port
  • Optional RS485 / SNMP / AS400communication port and SMS alarms
  • OptionalN+X redundancy parallel up to 6 units
  • Optional battery temperature compensation, EMD environmental sensors
  • Dowload AP9300 10 kVA ~ 30 kVA (3:3) Datasheet
  • Dowload AP9300 10 kVA ~ 30 kVA (3:3) User Manual
MODEL AP9310S(H) AP9315S(H) AP9320S(H) AP9330S(H)
Capacity 10 kVA / 9 kW 15 kVA / 13.5 kW 20 kVA / 18 kW 30 kVA / 27 kW
INPUT
Rated voltage 360 V / 380 V / 400 V / 415 Vac
Voltage range

277 ~ 485 Vac (no derating)

190 ~ 277 Vac (linear derating between 50% and 100% load)
Rated frequency 50 / 60 Hz (auto-sense)
Frequency range 40 ~ 70 Hz
Power factor  ≥ 0.99
Bypass voltage range -40% ~ +15% (settable)
Total harmonic distortion (THDi) ≤ 5%
OUTPUT
Voltage 360 / 380/ 400 / 415 Vac (settable)
Voltage regulation ± 1%
Frequency 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
Waveform Sinusoidal
Power factor 0.9
Total harmonic distortion (THDv) ≤ 2% (linear load); ≤ 5% (non-linear load)
Crest factor 3:1
Overload (Inverter)

102% ~ 125% for 10 min, 125% ~ 150% for 1 min, > 150% for 0.5 s

Overload (Bypass)

102% ~ 125% for 20 min, 125% ~ 150% for 2 min, > 150% for 1 s

BATTERIES
DC voltage Standard model: 240 Vdc; Long time model: 192 Vdc (168 / 192 / 216 / 240 V optional)
Inbuilt battery of standard model 20 × 7 Ah 40 × 7 Ah 40 × 9 Ah 60 × 9 Ah
Charging current
Long time model: 7 A supplied (additional 7 A is optional)
Standard model:  1 A, 2 A, 3.5 A settable
Recharge time

Standard model: 90% capacity restored in 4 hours;

Long time model: depend on the capacity of battery
SYSTEM
Efficiency ≥ 93%, ECO mode 98%
Transfer time 0 ms
Max. parallel numbers 6
Protections Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Communications RS232 / USB (standard), RS485 / dry contacts / SNMP (optional)
Display LCD + LED
Standards

EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11,

IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6,

IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2

OTHERS
Operating temperature 0℃ ~ 40℃
Storage temperature -25°C ~ 55°C (without batteries)
Relative humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1000 m, derating 1% for each additional 100 m
Noise level at 1 m ≤ 60 dB ≤ 65 dB
Online thermal dissipation 3504 BTU/hr 5773 BTU/hr 8281 BTU/hr 9929 BTU/hr
Dimensions (W × D × H) (mm) 350 × 655 × 732 (H)
350 × 785 × 858 (S) 350 × 785 × 1078 (S)
Packaged dimensions (W × D × H) (mm) 472 × 780 × 920 (H)
472 × 910 × 1050 (S) 472 × 910 × 1260 (S)
Net weight (kg) 55 (H), 110 (S) 60 (H), 155 (S) 61 (H), 175 (S) 65 (H), 235 (S)
Gross weight (kg) 65 (H), 125 (S) 70 (H), 170 (S) 71 (H), 190 (S) 75 (H), 250 (S)

● Derate capacity to 90% when the output voltage is adjusted to 360 Vac.

● S means standard model, H means long time model.

● All specifications are subject to change without notice.